The safety ventilation louvres type HS (High Safety) are specially designed for additional burglary protection when naturally ventilating transformer and gas spaces. Available with class 2 and class 3 burglar resistance certification according to NEN-5096 and EN-1627, this louvre retains its properties:
rainproof (see test data)
(dust) snow and dust resistant (see test data)
safe-proof
burglar-resistant WK2 WK3 RC2 RC3
Flame-extinguishing
mouse-tight
maintenance-free
one metallic whole for grounding
vandal-proof
condensate drain
As a result, people, animals, equipment and machines are optimally protected.
The various components of the JAZO air vents are assembled and welded at the front and / or rear. As a result, a metallic whole is created, as a result of which requirements with respect to grounding can be met in a simple manner. One earth-litze is sufficient.
There is a choice of various types of framing profiles. Mounting the ventilation louvre is possible in every architectural detail. Also available in stainless steel.
Pressure loss
EFD simulation
Features
Wert
Pitch
36 [mm]
Build-in depth
25 [mm]
Drag coefficient in
97.6
Drag coefficient out
110.7
Nettflow
27 [%]
pressure loss according to EFD.Pro
V in/out (m/s)
effectiveness (%)
0,00
93,00
0,50
80,00
1,30
52,00
2,00
35,00
2,80
21,00
sandblasting according to NEN-EN 13181: 2001, BSRIA
V in/out (m/s)
rain
0,50
A
1,00
B
1,50
D
2,00
D
2,50
D
rain penetration classes according to NEN-EN 13030, BSRIA