You are here:
JAZO TRAFO DOOR HS50 EW60 ENEX T6 2500 RR
Back to overview

JAZO TRAFO DOOR HS50 EW60 ENEX T6 2500 RR

Article number: JZEN-6-2500

Assembly service

Our craftsmen assemble the products on site so that you are assured of a perfect end result.

Before we start assembling, we first come to the construction site to view the situation and measure everything again.

In the shopping cart you can indicate that you want to use the assembly service.

JAZO TRAFO DOOR HS50 ENEX T6 2500 EW60 RR
Double door with top grille for Enexis customer station type 6 to 2500kVA with steel P-frame size 2700x3048mm (wxh). Pedestrian door on the right. The door and top grille are fitted with aluminum safety grille type HS50, with stainless steel fire-resistant cassettes mounted behind it. The whole has a net ventilating surface of 26,690 cm² and meets the fire resistance class EW60 according to NEN-EN 1634-1. Surface treatment: hot-dip galvanized with powder coating in RAL color of your choice (cassettes untreated). Equipped with facilities in accordance with Enexis regulations:

Wicket door is equipped with:

  • Lock: Forster 917908 with panic function (lev. JAZO) suitable for 17mm euro profile cylinder
  • Cylinder: (not for lev. JAZO) single-sided 17mm euro profile cylinder 10mm extended center cylinder 1017mm OK door
  • Fittings: (for lev. JAZO) outside: AMI security fittings (fixed knob on outer shield) inside: AMI security fittings (handle can be turned on blind inner shield)
  • Sign for warning sticker Enexis.
  • Nylon door position limiter
  • Door closer Dorma TS-83.
  • Earthing M8 incl. earth wire 25mm² (1040mm OK frame)
  • Fire-resistant cassette behind ventilating part(s) (made of untreated, perforated stainless steel)

Fixed door is equipped with:

  • edge slider
  • Nylon door position limiter
  • Earthing M8 incl. earth wire 25mm² (1040mm OK frame)

Warning sticker Enexis is supplied and installed by Enexis.

JAZO drawing: ST39290
JAZO article number: JZEN-6-2500

Note: dimensions deviate from the Enexis drawing. This is due to the minimum required amount of ventilation.

Features Wert
Pitch 59.5 [mm]
Build-in depth 66.5 [mm]
Drag coefficient in 26.19
Drag coefficient out 30.97
Nettflow 50 [%]
pressure loss according to EFD.Pro
V in/out (m/s) effectiveness (%)
0,00 88,00
0.00 88.00
0,50 74,00
0.50 74.00
1,30 40,00
1.30 40.00
2,00 17,00
2.00 17.00
2,80 9,00
2.80 9.00
sandblasting according to NEN-EN 13181: 2001, BSRIA
V in/out (m/s) rain
0,50 A
0.50 A
1,00 A
1.00 A
1,50 B
1.50 B
2,00 D
2.00 D
2,50 D
2.50 D
rain penetration classes according to NEN-EN 13030, BSRIA
Downloads