You are here:
Enexis type 6 to 2000 kVA transformer space
Back to overview

Enexis type 6 to 2000 kVA transformer space

Article number: JZEN-6-2000

Pui HS-50 for transformer up to 2000 kVA Enexis.

Enexis drawing: Type 6.
JAZO drawing: ST39256
JAZO article number: JZEN-6-2000

Fire-resistant door meets the fire resistance class E60 EW60 in accordance with NEN-EN 1634-1.

Wicket door is provided with:
- Lock: Forster 917908 with panic function (JAZO)
suitable for 17mm Euro profile cylinder
- Cylinder: (not for JAZO)
single sided 17mm Euro profile cylinder
10mm extended
heart cylinder 1017mm OK door
- Fittings: (for JAZO)
exterior: AMI safety fittings
(fixed button on outside shield)
inside: AMI safety fittings
(stool lockable on blind inside shield)
- Plate for warning sticker Enexis.
- Nylon door position limiter
- Door closer Dorma TS-83.
- Earthing M8 incl. Earth-light 25mm² (1040mm OK frame)
- Fireproof cassette behind ventilating part (s)
(executed in untreated, perforated stainless steel)

Fixed door is provided with:
- Kantschuif
- Nylon door position limiter
- Earthing M8 incl. Earth-light 25mm² (1040mm OK frame)

Warning sticker Enexis is delivered and assembled by Enexis.

Features Wert
Pitch 59.5 [mm]
Build-in depth 66.5 [mm]
Drag coefficient in 26.19
Drag coefficient out 30.97
Nettflow 50 [%]
pressure loss according to EFD.Pro
V in/out (m/s) effectiveness (%)
0,00 88,00
0,50 74,00
1,30 40,00
2,00 17,00
2,80 9,00
sandblasting according to NEN-EN 13181: 2001, BSRIA
V in/out (m/s) rain
0,50 A
1,00 A
1,50 B
2,00 D
2,50 D
rain penetration classes according to NEN-EN 13030, BSRIA
Downloads
Need more advice ?

Do you need specific ventilation calculations? Feel free to contact us. You can also contact us for all your technical and project specific questions.

Need advice ?