Description:
An aluminium double door for a 1600kVA configuration AC5 indoor transformer station according to the regulations of grid operator Liander. Composed of an aluminium P-frame, frame size 1980x3000mm (wxh) with a total door daylight size of 1876x2420mm (wxh). Completely fitted with an aluminium surface-mounted grille type HS-50R with a gross passage of 37,000cm² / net 18,850 cm². The door is right-hand outward-opening.
Specifications:
Pedestrian door is equipped with:
Fixed door is equipped with:
Features:
Rainproof, Snow and dustproof, Sandproof, Puncture-proof, Flame-retardant, Mouse-proof, Maintenance-free, One metallic unit for grounding, Vandal-proof and condensate draining.
Drawing number JAZO: AD42978
Surface treatment:
Provided with a sustainable environmentally friendly pretreatment. Powder coating in RAL colour of your choice. The warranty period for this is 5 years (only valid with correct compliance with the maintenance instructions) with corrosion class C2 according to ISO 12944-2.
Do you need specific advice regarding access and shielding of technical rooms? Feel free to contact us without obligation. You can also contact us for all your ventilation calculations.
Features | Wert |
Pitch | 59.5 [mm] |
Build-in depth | 66.5 [mm] |
Drag coefficient in | 26.7 |
Drag coefficient out | 23,6 |
Nettflow | 50 [%] |